Find out what the frequency response market is in Great Britain, how it works, how much you could earn from trading and how to join.

Your commercial battery and, if applicable, solar setup already save your company money by providing power to your site during periods when grid electricity is more expensive. You may also already earn an income by selling surplus energy back to the grid. But there are other markets you can take part in to bring in revenue, including the frequency response service market.

In this article, find out what frequency response is, how the market works, how much your business could earn and how you can join.

What is frequency response?

The frequency response market is operated by the National Energy System Operator, or NESO.

The electrical current flows through the grid backwards and forwards. Each complete back-and-forth movement is one cycle. In Great Britain, this happens 50 times a second, giving a frequency of 50 hertz (Hz). The electrical equipment connected to the grid has been designed to work at this frequency.

But if there is too much demand for electricity, that frequency falls. Conversely, if there is too much supply, that frequency rises.

The frequency response market pays providers to make rapid, automatic changes to electricity supply or use. For example, when frequency falls, a battery can discharge electricity to the grid to offset the shortfall in supply. When frequency rises, it can take electricity from the grid to charge.

You can take part in this market through an energy aggregator like GridVolt, a company that combines the battery power available at several businesses.

It arranges the service with NESO and checks that your battery and controls can provide it. The aggregator collects any payment from NESO and passes on your agreed share after its fee.

What trades are available through frequency response services?

Here’s how four different businesses might respond to a trading opportunity in the frequency response service market:

Example businessWithout the responseBattery’s response
Depot: falling frequencyThe battery keeps charging from the grid.The controls reduce charging, so the depot takes less electricity from the grid.
Factory: falling frequencyThe battery supplies some of the machinery’s electricity.The battery supplies more electricity, so the factory takes less from the grid.
Warehouse: rising frequencyThe battery keeps charging as planned.The controls increase charging, so the warehouse takes more electricity from the grid.
Cold store: rising frequencyThe battery supplies part of the refrigeration’s electricity.The battery supplies less, so the grid supplies more and the stored electricity stays available for later.

There are four main response services in this energy flexibility market:

ServiceWhat NESO uses it forFull response withinAble to sustain full response for
Dynamic Containment (DC)It contains a frequency change after a sudden loss of generation or demand.1 second15 minutes
Dynamic Moderation (DM)It controls rapid frequency changes during normal operation.1 second30 minutes
Dynamic Regulation (DR), aloneIt corrects smaller, continuing frequency changes.10 seconds60 minutes

In this table, a full response meaning delivering all the power agreed for the service, delivered when there is a frequency change.

Before entering your battery into a service, your aggregator checks that it has enough stored electricity or empty storage space to deliver the full response for the time NESO requires. If you offer to respond to both rising and falling frequency, your battery needs both.

What does a frequency response trade look like?

​​There are three steps in a frequency response trade, starting with informing NESO of what your group’s batteries could do, when and at what price.

What does your aggregator agree with NESO?

Your energy aggregator submits an offer in NESO’s auction. It states:

  • Which service it will provide, such as Dynamic Containment, Dynamic Moderation or Dynamic Regulation.
  • Whether the batteries will respond to falling or rising frequency. NESO buys these separately.
  • How much the batteries can increase or reduce their power.
  • Which four-hour periods it’s offering and at what price.

For example, let’s say, including your battery, the aggregator has the batteries at nine other businesses in the same virtual power plant. These ten businesses whose batteries can each reduce charging by 100 kilowatts (kW) could together take 1,000 kW less from the grid, a reduction of one megawatt (MW).

If NESO accepts the offer, your aggregator agrees to keep the ten batteries available for the four-hour period. During those hours, their controls automatically reduce charging as frequency falls, without waiting for a separate NESO instruction each time.

Your aggregator manages charging between responses so the batteries can keep providing the agreed service throughout the period.

How is the battery’s performance checked?

NESO has accepted your aggregator’s offer, so your battery’s controls are set to respond automatically to falling frequency during the agreed four hours.

Your aggregator also plans when to charge your battery, taking account of its stored electricity and your business’s needs. Let’s say it sets charging at 40 kW to store electricity for later use. That rate, before any frequency response, is its performance baseline.

While the battery is charging at 40 kW, its controls detect a fall in frequency. Under the agreed service rules, this fall requires a 30 kW reduction, so the controls reduce charging to 10 kW.

Your aggregator then checks the meter readings to confirm that charging fell by 30 kW within the required time.

How do you get paid?

NESO pays your aggregator for keeping the agreed amount of power available throughout the contracted hours. There’s no extra payment each time the battery responds. Your aggregator passes on your agreed share after its fee.

The auction sets the clearing price, which may be different from the price your aggregator offered. At a positive price, NESO pays the aggregator. At zero, neither pays the other for availability. At a negative price, the aggregator pays NESO.

An aggregator might accept a zero or negative price for one service if it can earn enough from another service provided alongside it.

For example, it could pay NESO to provide a response to rising frequency while receiving a larger payment for providing a response to falling frequency. It still needs to account for electricity costs, battery wear and its fee before deciding whether taking part is worthwhile.

How much could your business earn from frequency response?

The amount you earn from a frequency response trade depends on the value of the trade, the payment the aggregator takes, extra electricity costs, and savings you give up, like charging your battery when electricity is cheap and using it when prices are higher.

The examples assume:

  • Ten businesses each provide 100 kW for four hours, with all batteries available and responding correctly.
  • NESO pays £10 per MW per hour for each direction. Each business gets 10% of the group payment, less a 20% aggregator fee.
  • Batteries charge from the grid and supply their own businesses. Every 10 kWh bought provides 9 kWh after losses. Wear costs 2p per kWh discharged.
  • Controls and metering are installed, with no extra fixed charges.

Each comparison includes recharging to finish with the same stored electricity. All figures are assumed, exclude VAT and tax, and aren’t GridVolt terms or earnings forecasts.

The table shows how each business’s payment is calculated. The three examples then show what it keeps after costs and lost savings.

Payment calculationA. Quiet periodB. More active periodC. Existing savings given up
Group’s contracted serviceDC, falling frequencyDM, both directionsDC, falling frequency
Group’s contracted power1 MW1 MW in each direction1 MW
Gross NESO payment1 × 4 × £10 = £40(1 × 4 × £10) + (1 × 4 × £10) = £801 × 4 × £10 = £40
Business’s 10% allocation£4£8£4
Aggregator’s 20% fee−£0.80−£1.60−£0.80
Payment to the business£3.20£6.40£3.20

In Example B, the aggregator agrees to provide a response if frequency rises or falls during the same four hours. NESO pays separately for each. At our assumed price of £10 per MW per hour for both, the group receives £80 instead of £40.

1. The battery stays ready and does little work

A business has electricity stored in its battery that it won’t need during the four-hour window. It agrees, through its aggregator, to supply electricity from the battery to its building if grid frequency falls.

Frequency across the grid remains steady throughout, so the battery only supplies 2 kWh to the building during that time. The business buys 2 kWh less from the grid as a result.

Afterwards, the battery recharges, taking slightly more than 2 kWh from the grid to replace what it supplied because some electricity is lost during charging and discharging. Electricity costs 20p per kWh throughout.

CalculationAmount
Payment to the business£3.20
Electricity bought to replace the charge2 ÷ 0.90 = 2.222 kWh
Cost of recharging2.222 × £0.20 = £0.444
Grid purchases avoided2 × £0.20 = £0.40
Additional electricity-bill cost£0.444 − £0.40 = £0.044
Overall additional benefit£3.20 − £0.044 = £3.16, rounded

The business receives £3.20 for agreeing to supply electricity from its battery if frequency falls. Recharging costs about 4p more than it saved by using battery electricity instead of grid electricity, so the company ends up £3.16 better off.

2. The battery charges and discharges during the service

One company, with a partly charged battery, won’t need to draw power from it during the four-hour windows. But, through its aggregator, it agrees to charge the battery if grid frequency rises and supply electricity to its building if frequency falls. Otherwise, it would leave the battery unused during those hours.

In the four-hour windows, frequency rises and falls, so the battery charges at some points and supplies the building at others.

Including recharging afterwards, the battery takes 50 kWh from the grid and supplies 45 kWh to the building. The business therefore buys 45 kWh less directly from the grid to power its equipment.

The battery finishes with the same amount of stored electricity it started with. The 5 kWh difference is lost during charging and discharging. Electricity costs 20p per kWh throughout.

CalculationAmount
Payment to the business£6.40
Electricity bought to charge the battery50 × £0.20 = £10
Saving from using battery electricity in the building45 × £0.20 = £9
Extra electricity-bill cost£10 − £9 = £1
Overall additional benefit£6.40 − £1 = £5.40

The business spends £10 charging the battery and saves £9 by using the stored electricity instead of buying directly from the grid. The £1 difference covers the electricity lost during charging and discharging. After taking that cost from its £6.40 payment, the business is £5.40 better off.

3. The contract gives up an existing bill saving

A business normally uses its battery to supply 50 kWh to its building when grid electricity costs 30p per kWh. It recharges later when the price falls to 10p per kWh.

Its aggregator offers the battery’s full 100 kW of discharge power to NESO for those same four hours. To keep that power available if frequency falls, the business gives up its usual use of the battery to cut its bill.

In this example, the frequency stays within the range where NESO doesn’t need a response. The battery supplies no electricity, so the business buys the building’s electricity from the grid at 30p per kWh. It receives £3.20 for the service.

CalculationAmount
Grid electricity the battery normally replaces50 × £0.30 = £15
Electricity needed to recharge afterwards50 ÷ 0.90 = 55.556 kWh
Usual recharging cost55.556 × £0.10 = £5.556
Bill saving given up£15 − £5.556 = £9.44, rounded
Payment for the service£3.20
How much worse off the business is£9.44 − £3.20 = £6.24

The business receives £3.20 but gives up a £9.44 saving on its electricity bill. It finishes £6.24 worse off. On these figures, the aggregator should offer less battery power or choose different hours so the business can keep more of its usual saving.

How can your business take part in frequency response?

Here are the three steps you need to follow to begin taking part in frequency response trades.

1. Find an aggregator to assess your battery

Ask the aggregator which frequency response services it offers and whether it can control your battery through your inverter. Give it your equipment details and recent electricity-use data so it can assess your setup.

It will check:

  • How much power your battery can draw from the grid when charging or supply to your building when discharging.
  • How many seconds it takes to reach the required charging or discharging rate after a frequency change.
  • How many minutes it can charge or discharge at that rate before it fills up or runs out of usable electricity.
  • Whether your meters can record the readings needed to prove the battery delivered the agreed response.

Your aggregator can combine your battery with others to meet NESO’s minimum requirement of 1 MW per registered unit. The sites must be within the same electricity-market region, called a Grid Supply Point (GSP) Group, and NESO must approve the arrangement.

2. Agree when and how your battery can be used

Tell your aggregator when your business needs to use its stored electricity and how much you need to keep in reserve. If you have solar panels, tell your aggregator what times of day you need space in the battery to store the electricity they generate.

Your aggregator checks:

  • Your battery’s operating limits and warranty conditions.
  • How much power your site is allowed to take from or send to the grid.
  • Whether your local network operator can restrict battery use under a flexible connection agreement.

The answers determine how much battery power the aggregator can offer NESO and at what times. You agree to these limits before it submits any offers. It should explain how it will manage charging and discharging between responses while keeping enough electricity for your business.

3. Check the agreement and complete the setup

Agree how much of the payment from the NESO you’ll receive (minus the charge from the aggregator) and when you’ll be paid. Ask for statements showing how it works out your payment.

Also check whether the aggregator can reduce your payment or charge you if your battery:

  • Fails to provide the service
  • Responds too slowly
  • Supplies too little power
  • Has missing or incomplete meter readings

Tell the aggregator about any other trading or flexibility services you use because it needs to check that it doesn’t offer any battery power you’ve already agreed to provide somewhere else. Agree how you’ll report faults and planned maintenance.

Once you’ve agreed the terms, the aggregator arranges the tests, metering, control connections and registration needed before it starts to offer your battery’s power in NESO’s auctions.

What other electricity markets and flexibility services are available?

Other options in the flexibility market suit different equipment actions and payment arrangements.

  • Demand Flexibility Service. Take more or less electricity from the grid during agreed periods arranged through a registered provider.
  • Local flexibility markets. Supply electricity or use more or less to help your local network operator manage pressure on its network.
  • Balancing Mechanism. Supply more or less electricity, or take more or less from the grid, following an instruction at short notice.
  • Reserve services. Keep suitable equipment ready to supply electricity or use more or less when NESO requests it.
  • Capacity Market. Keep equipment ready to supply electricity or reduce grid use when Britain’s electricity supplies are stretched.
  • Wholesale electricity market. Sell electricity from your battery through a trading arrangement, earning from the trade.

How can GridVolt help you assess your battery?

If you already have a solar + battery or battery-only setup, GridVolt can assess whether frequency response could be an option for your business. We’ll check your equipment and electricity use, including how much stored electricity you need for your own work.

Energy Manager controls compatible equipment through an on-site gateway that passes data and instructions between your setup and our software.

We’ll explain which services are available to your site, who would arrange the trades with NESO and what you could keep after fees and electricity costs.

Fill out the form on the right or contact GridVolt to discuss your options.

Frequently asked questions

Is frequency response the same as reserve?

No. In the dynamic services described here, your battery follows the measured frequency automatically. With reserve services, NESO sends an instruction to activate the service. What triggers the action is different.

Does DR always have ten seconds to reach full response?

No. Ten seconds applies to DR on its own. If the same unit provides DR alongside DC or DM, the one-second full-response requirement applies. Your aggregator needs to qualify the combined setup.

How frequent are the operating and performance readings?

Your aggregator records operating data once a second and sends it to NESO with no more than five seconds’ delay. Aggregators normally record 20 performance measurements a second, or two a second for standalone DR. Those readings show rapid power movements, while billing readings show electricity bought or exported.